DF MANUAL FAULTS
Manual version 2.0 (26-10-2012) en-35
en
See also:
2.7.2 "Control panel settings" on page 18
2.7.3 "External control input" on page 19
2.7.5 "Unit settings" on page 20
2.7.6 "Multiple units operated from one control panel" on
page 21
6.3 "Fuses" on page 39
6.4 "Temperature cut-out" on page 39
The unit (or part of the unit) is
blowing cold air.
The LEDs on the control panel are
flashing.
For electrically heated units:
The temperature cut-out has
turned the unit (or part of the unit)
off to prevent overheating.
w This may indicate a seri-
ous fault that may be
hazardous.
This fault can also occur if the unit
has been powered down for a short
while.
1. Check and reset the tempera-
ture cut-out.
2. Check the fans. If one or more
fans do not work, check:
the fan wiring;
control PCB connections
•control PCB fuses
3. If these are okay, then replace
the fan.
Discharge air is not hot enough. For water-heated units:
The supply water temperature is
too low.
Raise the central heating system’s
water temperature.
For electrically heated units:
One or more phases on the power
supply have tripped out.
Check the power supply’s fuses and
electrical connections.
The unit continues to blow hot air. For water-heated units:
The valve has been opened manu-
ally.
Turn the handle to the ‘AUTO
position.
The unit always blows cold air in
automatic mode.
The temperature sensor is not
working.
1. Check Connector J3 on the con-
trol PCB.
2. Replace the sensor.
If multiple units have been con-
nected to a single control panel:
Units are heating unevenly in auto-
matic mode.
The temperature is set indepen-
dently in each unit.
Configure one unit as a master.
P
ROBLEM POSSIBLE CAUSE RESOLUTION